Certified Inverter Datasheet & Grid Compliance Assessment

INGETEAM POWER TECHNOLOGY SA INGECON SUN 1165TL U B420 {420V} (1165.0 kW) Inverter

Sandia simulation models, California Energy Commission (CEC) test results, and MPPT string sizing specifications.

Rated AC Output
1165.00 kW
Continuous active power
Weighted Efficiency
97.48%
CEC / Sandia curve rating
MPPT Voltage Window
610–740 V
Max DC limit: 740V
Architecture
Hybrid Storage Inverter
Hybrid Storage Capable

Solerz Inverter Engineering & Sizing Analysis

1. MPPT Voltage Tracking Dynamics & String Boundaries

The INGETEAM POWER TECHNOLOGY SA INGECON SUN 1165TL U B420 {420V} incorporates a precision Maximum Power Point Tracking (MPPT) voltage window of 610V to 740V DC, paired with an absolute maximum DC input voltage of 740V. To prevent inverter shutdown or destructive overvoltage damage during cold winter mornings (-15°C to -30°C), array strings must be strictly designed so that the temperature-corrected open-circuit voltage (Voc_cold) does not breach 740V. Conversely, under hot summer conditions (+65°C cell temperature), string Vmp must remain comfortably above 610V to avoid low-voltage MPPT clipping.

2. DC/AC Inverter Loading Ratio (ILR Oversizing)

With a rated continuous AC power of 1165.00 kW, this inverter delivers optimal Levelized Cost of Energy (LCOE) when paired with a DC array capacity of 1572.8 kWp (1.30x – 1.35x Inverter Loading Ratio). Oversizing the PV array ensures the inverter operates in its highest efficiency sweet spot during morning and afternoon shoulder hours, while absorbing midday clipping losses that are economically offset by increased total annual kWh production.

3. Grid Compliance & Interconnection Standards

Engineered in compliance with UL 1741 SB / IEEE 1547-2018 standards, the unit supports advanced autonomous grid-support functions, including dynamic Volt-VAR reactive voltage regulation, Volt-Watt overvoltage curtailment, and frequency ride-through. Total Harmonic Current Distortion (THD) is maintained strictly below 3%, preventing harmonic noise injection into local utility distribution transformers.

Electrical Specifications & Operating Parameters
Rated AC Power Output (Paco)1165000 W (1165.00 kW)
Nominal AC Grid Voltage (Vac)420 V
Weighted Conversion Efficiency97.48 %
Maximum DC Input Voltage (Vdcmax)740 V
MPPT Voltage Tracking Range610 – 740 V
Max Continuous Input Current (Idcmax)1770.48 A
Night Tare Loss (Pnt)80.00 W
Storage CouplingHybrid DC/AC Battery Coupled
Browse All Inverters Calculate MPPT Array Matching Inverter IEEE Standards Handbook